Product Search
 
 

AP & APR

< back

APR

DIN mount split core AC current transducers based on PRiME.

Main characteristics:

  • Current range from 10A to 400A selectable
  • RMS (AP) or True RMS (APR) version
  • Several output : 4-20mA and 0-5V or 0-10V selectable
  • 1% accuracy
  • 0.5% linearity
  • Wide bandwidth up to 6kHz

Features:

  • AC currents measurements with galvanic isolation
  • Power supply +24VDC or loop powered (4-20mA version)
  • Isolation test voltage : 5KVRMS / 50 HZ / 1 min
  • Temperature range -20°C to +60°C
  • Low weight: 90g
  • UL94-V0 recognized materials

Standard compliance:

 

  • The products are CE certified regarding their electromagnetic compatibility according to the European Directive 2004/108/EEC and tested according to the standard IEC 61326.
  • The products are CE certified regarding their Safety according to the European Directive 2006/95/EEC and tested according to the standard IEC 61010-1.

Remarks:

  • By using PRiME technology improve performances (accuracy, linearity, bandwidth) compared to traditional current transformers using magnetic circuit.
  • A new and unique mechanical design, combination of split core and DIN rail mounting.
  • Current sensor and transducer in a single package.

 

Product search results
Model Expand Primary
Nominal
Value
Primary
Signal
Type
Signal
Conditioning Type
Aperture Dimension (mm) Case Type Standard Output Type
 
AP 100 B10 expand 50 A, 75 A, 100 A AC RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
AP 100 B420L expand 50 A, 75 A, 100 A AC RMS ø18 mm Split core 4-20 mA
AP 200 B10 expand 100 A, 150 A, 200 A AC RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
AP 200 B420L expand 100 A, 150 A, 200 A AC RMS ø18 mm Split core 4-20 mA
AP 400 B10 expand 200 A, 300 A, 400 A AC RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
AP 400 B420L expand 200 A, 300 A, 400 A AC RMS ø18 mm Split core 4-20 mA
AP 50 B10 expand 10 A, 25 A, 50 A AC RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
AP 50 B420L expand 10 A, 25 A, 50 A AC RMS ø18 mm Split core 4-20 mA
APR 100 B10 expand 50 A, 75 A, 100 A AC True RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
APR 100 B420L expand 50 A, 75 A, 100 A AC True RMS ø18 mm Split core 4-20 mA
APR 200 B10 expand 100 A, 150 A, 200 A AC True RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
APR 200 B420L expand 100 A, 150 A, 200 A AC True RMS ø18 mm Split core 4-20 mA
APR 400 B10 expand 200 A, 300 A, 400 A AC True RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
APR 400 B420L expand 200 A, 300 A, 400 A AC True RMS ø18 mm Split core 4-20 mA
APR 50 B10 expand 10 A, 25 A, 50 A AC True RMS ø18 mm Split core 0-5 VDC,
0-10 VDC
APR 50 B420L expand 10 A, 25 A, 50 A AC True RMS ø18 mm Split core 4-20 mA